In the table above, the first column represents example display
indications, in the next columns there are: parameter description, minimal
amount, maximum amount allowed to set, step of the parameter during
the setup, factory defaults, to which you can return by choosing [Prod]
option.
4.1. Pressure fan work parameters
Fan power [Π100] - this value defines power of the fan. When
"Πr"parameter is set to "0-10" this is the maximum power of the fanwhich
can be achieved during automatic fan control.
Automatic fan speed control [Πr 1] - it is on, when this parameteris set to
"0-10" and causes automatic fan speed decrease whentemperature of
water in the boiler reaches desired temperature.If this parameter is set to
"-", the fan automatic smooth speedcontrol is disabled and the fan can
work with power set by "Π" parameter. Setting parameter value in range
from 0 to 10 meanstime in minutes of the smooth fan speed increase from
40% tovalue of "Π" for smooth boiler start.
Fan work time [Πn 5] - time of turning the fan on for a while, to remove
accumulated gases. Setting the parameter to "-" turns this function off.
This function can be active in WORK mode.
Fan pause time [Πu 6] - time between fan work periods
4.2. Circulating pump parameters
Circulating pump launch temperature [P144] - temperature of water in the
boiler, which causes start of the circulating pump. Circulating pump works
independently from the control process and is launched additionally in
case of boiler overheat.
Circulating pump launch hysteresis [Ph 4] - this parameter defines what
value should temperature decrease by, below circulating pump launch
temperature, to turn the pump off.
Pause time between circulating pump 30 second work periods [Pc 2]- in
STOP mode or when room thermostat circuit is open, the circulating pump
is launched for 30 seconds, to mix water in heating circulation. This
parameter defines time between launches of the pump.
Setting the parameter to "-" turns this function off.
4.3. Boiler work temperature setting
Minimal boiler temperature [L150] - minimal temperature, which you can
set with the boiler thermostat knob.
Maximum boiler temperature [H195] - maximum temperature, which you
can set with the boiler thermostat knob.
Boiler temperature hysteresis [h 10] - this parameter defines what value
should temperature of water in the boiler decrease by, below temperature
set with the thermostat knob, to turn the pressure fan on.
4.4. Boiler overheating protection
Boiler overheating temperature [A210] - value, exceeding which causes
permanent turn off of the pressure fan and launch of the circulating pump,
to prevent boiler overheating. Overheating mode is indicated by boiler
overheating indicator and by displaying error [E 2] on the display. It can
be turned off by pressing STOP button, but only when temperature
decreases below boiler overheating temperature.
Pressure fan turning off occurs also in case of damage of the boiler
temperature sensor, which is displayed on the display by error [E 1].
STB - the controller has also additional protection from overheating, which
is independent from the processor, . In case of temperature increase over
200°F, the control process is turned off by turning the fan off and launching
the circulating pump. The fan and the pump are joined to the control
process again, when temperature reaches 190°F.
STB circuit enables more precise boiler work control and reduces
overheating possibility.
4.5. No fuel
No-fuel testing time during fuel firing start [Fd60] - after switching to
WORK mode, if water temperature doesn't reach temperature set with the
thermostat in programmed time, the control process will be turned off and
the display will show the message: [FUEL].
You can return to previous mode by pressing STOP button.
No-fuel testing time during work mode [Fb30] - in WORK mode, if
temperature of water in the boiler decreases below temperature set with
the thermostat, by hysteresis value, and don't reach temperature set with
the thermostat in programmed time, the control process will be turned off
and the display will show the message: [FUEL]. You can cancel the alarm
by pressing STOP button.
4.6. Additional output work mode [Ar 0] - the controller has
beenequippedwith a multipurpose output that can work in one of following
modes:
- mode [Ar 0] - output may control the oil or gas boiler if such boilerexists
in the heating circuit.After switching the controller on with the main power
switch theadditional boiler is turned offand it turnes on again when there is
no fuel in the solid fuel boiler.This function is useful in heating systems
where a solid fuel boiler isused to cut the heating costs. After erasing the
no fuel alarm by pressing STOP button theadditionalboiler is again turned
off and the controller works again
- mode [Ar 1] - output may control the additional alarm signaling
system.Boiler temperature sensor malfunction, overheating and no fuel
alarmswill turn on the alarm
- mode [Ar 2] - output may control the mixing valve
servo-motor.Controlling the mixing valve requires room thermostat to be
present.Mixing valve is being opened and closed depending on the room
thermostatinput. Additionally, mixing valve is opened in case of
overheating or boilertemperature sensor malfunction.
CAUTION. Equipment should be connected to additional output using
UM-1module. Connection schemes are shoun on picture 3.
4.7. Testing of device's outputs
To make checking the controller work easier, it is possible to test output
circuits which control the fan and the pump, and the circuit which controls
additional boiler. This function is available in service mode, only if the
control process is off, i.e. the controller was in STOP mode before
switching to service mode. By choosing [outP] on the display and
pressing OK button you can turn on the circulating pump for a while, by
choosing [outΠ] and pressing OK you can turn on the pressure fan and by
choosing [outr] and pressing OK you can turn the additional boiler, the
alarm signaling system or the mixing valve servo-motor on (if the
additional module is connected).
4.8. Factory defaults
You can return to standard settings, set by the producer, by choosing
[Prod] option in service mode and pressing OK button. After activating this
function, the device sets each parameter showed in the table to default.
4.9. Exiting service mode
By choosing [End ] option on the display and pressing OK button you can
quit service mode. The device also quits service mode, when no buttons
are pressed for 1 minute.
5. Additional functions
To improve comfort in heated rooms, the device is equipped with input
allowing to connect any kind of room thermostat with contact output. When
temperature in the room is below desired temperature, the circulating
pump is turned on and the room thermostat indicator is lit.
It means that the boiler should keep temperature set by the room
thermostat. After reaching desired temperature in the room, the room
thermostat indicator turns off, the circulating pump is turned off and the
boiler switches to mode, in which it's keeping minimal temperature.
CAUTION. In case of not having room thermostat in the system, the room
thermostat input contacts must be short-circuited.
6. Device failures
The controller is constantly testing if its internal circuits and temperature
sensor are working correctly. After detection of fault, it stops the pressure
fan, turns on the circulating pump and shows proper error message on the
display. In case of failure please turn off the controller, plug the circulating
pump to the power source, bypassing the controller, ensure appropriate
fuel firing in the boiler and contact the service.
When [E 1] error appears on the display, it means fault (short-circuit) in
the boiler sensor circuit or temperature below 32°F. [E 2] is displayed if
boiler overheats. [E 3] error means fault and overheating at the same
time. Appearing of [E 1] error on the display without ability to cancel it by
pressing STOP button, in spite of temperature below 190°F, may mean
permanent damage of boiler temperature sensor (e.g. if the boiler
overheated above 300°F).